
VCM-X / RNE STATUS
VCM-X / RNE Operator Interface SD
56
VCM-X / RNE Status Screens
Status
From any menu screen, press <STATUS>. The Unit Selection Screen,
shown below, will appear requesting that you enter the unit ID number.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
*00*
Enter the correct unit ID number of the VCM-X or RNE Controller you
want to view and press <ENTER>. You must type in the number, even
if it is “1”. Once communication is established, the *00* at the bottom
will disappear. Then
press <>. You will then see Setpoint Screen #1.
Press
<ENTER> to save entered data and press <> to scroll through
the screens.
NOTE: If the *00* remains, it indicates a communication failure
to the controller.
Status Screen 1 - Mode
VCM-X / RNE v1.00
Occupied Mode
Vent Mode
02/15/10 05:00 PM
Line 2 Displays one of the following:
Unoccupied Mode Remote FRC Occupied
Occupied Mode Override Mode
Holiday Mode Zone Demand!
Forced Schedule Mode OUTPUT FORCE MODE!
SUPPLY AIR CUTOFF! High CO2 Level Mode!
Line 3 Displays one of the following:
Off Mode Dehumid. Mode Defrost Mode
Vent Mode Cool Dehumid. Mode
Cool Mode Heat Dehumid. Mode
Heat Mode Warm Up Mode
Line 4 Displays one of the following:
MM/DD/YY HH:MM XX (XX = AM or PM)
Fan Starting Delay and then time will display
xx Left in WarmUp (Number of Minutes Left)
Status Screen 2 - Cooling, Heating, Economizer
VCM-X / RNE v1.00
Cooling Enabled
Heating Enabled
Economizer Disabled
Line 2 Displays one of the following:
Cooling Enabled
Cooling Disabled
Line 3 Displays one of the following:
Heating Enabled
Heating Disabled
Line 4 Displays one of the following:
Economizer Enabled
Economizer Disabled
NOTE: On a non-Heat Pump unit confi gured for Make-Up Air
Control, the Heating and Cooling Lockouts are ignored,
so Heating and Cooling will always show enabled.
Status Screen 3 - Mode Enable Temperature &
Mode Cooling and Heating Setpoints
VCM-X / RNE v1.00
Enable Tmp.: XX.XºF
Cool Spt: XX.XºF
Heat Spt: XX.XºF
Line 2 Mode Enable Temperature
Can be the Supply Air Temperature, Return Air
Temperature, Outdoor Air Temperature, or Space
Temperature, depending on which one has been
confi gured as the Mode Enable Sensor.
Line 3 Cooling Mode Setpoint
Based on the current Occupied/Unoccupied Mode
of operation.
Line 4 Heating Mode Setpoint
Based on the current Occupied/Unoccupied Mode
of operation.
Comentarios a estos manuales