VCM-X / RNE SETPOINTS
VCM-X / RNE Operator Interface SD
48
Setpoint Screen #9 - Outdoor Air Lockouts
VCM-X / RNE Spts
Outdoor Air Lockouts
Cooling......: 50ºF
Heating......: 70ºF
The Unit Controller will Lockout Mechanical Heating or Cooling when
the Outdoor Air (OA) Temperature is above or below these Setpoints.
On Air to Air Heat Pump units, Compressor Cooling and Heating can
only operate if the OA Temperature is above the Outdoor Air Cooling
Lockouts. If using the VCM-X WSHP (Water Source Heat Pump) Con-
troller, the OA Cooling Lockout is ignored. Since Emergency Heat can
only be used below the Compressor Lockouts, Emergency Heat is there-
fore not available on WSHP units using the VCM-X WSHP Controller.
Description Minimum Default Maximum
OA Lockouts Cooling 0ºF 50ºF 100ºF
OA Lockouts Heating 50ºF 70ºF 150ºF
Setpoint Screen #10 - Cutoff Temperature
VCM-X / RNE Spts
Cutoff Temperatures
Lo SAT.......: 40ºF
Hi SAT.......: 170ºF
The Unit Controller will temporarily disable Heating or Cooling if while
in Heating or Cooling Mode the Supply Air Temperature rises above
the High SAT Cutoff Temperature Setpoint or falls below the Low SAT
Cutoff Temperature Setpoint. See the VCM-X Controller Technical
Guide, VCM-X Modular E-BUS Controller Technical Guide, or RNE
Controller Technical Guide for detailed information on the Low and
High Supply Air Temperature Cutoff sequence of operation.
Description Minimum Default Maximum
Lo SAT Cutoff 0ºF 40ºF 250ºF
Hi SAT Cutoff 0ºF 170ºF 250ºF
Setpoint Screen #11 - Minimum Supply Fan
VFD Speed For Heating
VCM-X / RNE Spts
Minimum Supply
Fan VFD Speed
For Heating..: 30%
If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.
VCM-X / RNE Setpoint Screens
Description Minimum Default Maximum
Min Supply Fan VFD
Speed For Heating
0% 30% 100%
Setpoint Screen #12 - Morning Warm Up Temp
VCM-X / RNE Spts
Morning WarmUp
Target Temp: 72º F
Max Length.: 60 Min
When the Unit Controller is confi gured for VAV operation and the con-
troller enters the Occupied Mode, the controller looks at the Return Air
Temperature to determine if the unit should initiate Morning Warm-up
Mode. If the Return Air Temperature is below the Morning Warm-up
Target Temperature and the Max Length is greater than “0,” the control-
ler will initiate Heating. This is considered Morning Warm-up and will
run until the Return Air Temperature rises above the Morning Warm-up
Target Temperature or until the Max Length Setpoint time expires.
Description Minimum Default Maximum
Morning Warm Up
Target Temp
50ºF 72ºF 90ºF
Morning Warm Up
Max Length
0 Min 60 Min 240 Min
Setpoint Screen #13 - Dehumidifi cation Indoor
RH & OA Dewpoint
VCM-X / RNE Spts
Dehumidification Spt
Indoor RH....: 50%
OA Dewpoint..: 55ºF
On VAV or CAV confi gured units that are not using 100% Outdoor Air,
when the Indoor Relative Humidity percentage rises above the Indoor
RH Setpoint, the unit will start operating in Dehumidifi cation Mode.
If an Indoor Humidity Sensor is installed, the unit will reset the Coil
Suction Temperature Setpoint as needed to maintain this Indoor RH
Setpoint. This includes VAV, C AV and MUA applications.
On MUA confi gured units that are using 100% Outdoor Air, when the
Outdoor Air Dewpoint Temperature rises above the OA Dewpoint Set-
point, the unit will start operating in Dehumidifi cation Mode.
Description Minimum Default Maximum
Dehumidifi cation Setpoint
Indoor RH
1% 50% 100%
Dehumidifi cation Setpoint
OA Dewpoint
35ºF 55ºF 80ºF