VCC-X Controller Code: SS1062 Version 2.0 & upVAV/Zone Controller Code: SS1001, SS1005, SS1025Requires Service Tool SD Code: SS1063Requires Sys
MODULAR SERVICE TOOL SD10 VCC-X Operator Interface SDModular Service Tool KeysOperator InterfacesIn order to confi gure and program the VCC-X Controlle
VCC-X Operator Interface SD MODULAR SERVICE TOOL SD11Modular Service Tool InitializationModular Service Tool Initialization Screen and
MODULAR SERVICE TOOL SD12 VCC-X Operator Interface SDSetting the Operating ModeThe Operating Mode is displayed on the last line of the Main Screen as
VCC-X Operator Interface SD MODULAR SERVICE TOOL SD13Modular Service Tool Alarm SearchNOTE: When you press the <ALARMS> button o
MODULAR SERVICE TOOL SD14 VCC-X Operator Interface SDThe screens will step through the Start Time and then the Stop Time for each day of the week. You
VCC-X Operator Interface SD MODULAR SERVICE TOOL SD15 Holiday Start/Stop TimesVCC-X Schd ID #Holiday Schedule Start Event #1: XXXX
ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD16System Manager SD Keys and ButtonsOperator InterfacesIn order to confi gure and progr
VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD17System Manager SD InitializationSystem Manager SD Initialization Screen and Setup ScreensA
ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD18Setting the Operating ModeSetting the Operating ModeThe Operating Mode is displayed
VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD19Changing PasscodesSystem Manager PasscodesChanging the mode of operation, updating software
ZoneZoneSD CARD UPDATING INSTRUCTIONSThe Modular Service Tool and Modular System Manager are equipped with an SD memory card. This SD card can be remo
ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD20Network Mode & Multiple Managers Loop SearchWhen the System Manager is confi gu
VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD21 Unit Alarm Search and Override SearchAlarm ScreenNO ALARMS DETECTEDTo check controllers indi
ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD22 Week SchedulesFrom the Unit Schedule Menu, select Week Schedules. The following t
VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD23 Holiday Start/Stop Day SelectionFrom the Unit Schedule Menu, select Holiday Schedules. Th
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD24VCC-X Confi guration Screen Index VCC-X Confi guration Screen IndexThe available Confi gurat
VCC-X Operator Interface SD VCC-X CONFIGURATION25 Confi guration ScreensIn order to correctly set up the VCC-X Controller, you must fi rst confi gure
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD26VCC-X Confi guration Screens Confi guration Screen #3 - RSM #3 & #4 Modules InstalledV
VCC-X Operator Interface SD VCC-X CONFIGURATION27 VCC-X Confi guration ScreensConfi guration Screen #9 - HVAC Mode Set By Remote ContactVCC-X Cnfg
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD28VCC-X Confi guration ScreensConfi guration Screen #15 - Return Sensor TypeVCC-X Cnfg I
VCC-X Operator Interface SD VCC-X CONFIGURATION29Confi guration Screen #22 - Fan Starting DelayVCC-X Cnfg ID #Fan StartingDelay: -1s[-1 = Unit A
VCC-X Operator Interface SD 3 TABLE OF CONTENTSOVERVIEW & SYSTEM CONNECTION ...
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD30VCC-X Confi guration ScreensConfi guration Screen #27 - Mechanical Heat/Cool Alarm DelayVC
VCC-X Operator Interface SD VCC-X CONFIGURATION31VCC-X Confi guration ScreensConfi guration Screen #33 - Economizer Voltage OutputVCC-X Cnfg ID #
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD32Confi guration Screen #39 - Exhaust Fan OutputVCC-X Cnfg ID #Exh Fan Volts Min Volt
VCC-X Operator Interface SD VCC-X CONFIGURATION33Confi guration Screen #43 - Type of Airfl ow Station VCC-X Cnfg ID #Airflow Station: ParagonUSE
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD34VCC-X Confi guration ScreensConfi guration Screen #50 - Return Airfl ow Duct Size VCC-X Cn
VCC-X Operator Interface SD VCC-X CONFIGURATION35Confi guration Screen #55 - Daylight Savings AdjustmentVCC-X Cnfg ID #Daylight AdjustmentStart
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD36VCC-X Confi guration ScreensConfi guration Screen #62 - Broadcast to BoxesVCC-X Cnfg
VCC-X Operator Interface SD VCC-X CONFIGURATION37VCC-X Confi guration ScreensConfi guration Screens #70-76 - VCC-X RelayConfi guration ScreensVCC-X C
ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD38VCC-X Confi guration Screens Table 5: User-Confi gurable Relay OutputsNo. Relay Descripti
VCC-X Operator Interface SD VCC-X CONFIGURATION39Screen #20 Mod Heat Proportional Window and Time PeriodScreen #21 Mod Cool Proportional Window
ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD4Modular Service Tool SD Modular Service Tool SDThe OE391-12 Modular Service Tool is a system
VCC-X SETPOINTS VCC-X Operator Interface SD40VCC-X Setpoint ScreensSetpoints - General Procedures Modular Service Tool InstructionsFrom any menu s
VCC-X Operator Interface SD VCC-X SETPOINTS41Setpoint Screen #4 - Mode DeadbandVCC-X Spts ID:#Mode DeadbandSetpoint: 1.0ºFThis Setpoint is added
VCC-X SETPOINTS VCC-X Operator Interface SD42Setpoint Screen #6 - Space Sensor Push-Button Override DurationVCC-X Spts ID:#Space Sensor PushBut
VCC-X Operator Interface SD VCC-X SETPOINTS43Setpoint Screen #10 - Indoor RH Setpoint Low and High Reset SourceVCC-X Spts ID:#Indoor RH Setpoint
VCC-X SETPOINTS VCC-X Operator Interface SD44VCC-X Setpoint ScreensSetpoint Screen #13 - VFD Speed Minimums Cool/Vent ModesVCC-X Spts ID:#VFD
VCC-X Operator Interface SD VCC-X SETPOINTS45Setpoint Screen #18 - Heat Reset Source Setpoints - High Reset/Low ResetVCC-X Spts ID:#Heat Rst Sourc
VCC-X SETPOINTS VCC-X Operator Interface SD46Setpoint Screen #19 - Stage Off Window - Cooling/HeatingVCC-X Spts ID:#Stage Off WindowCooling: 5.
VCC-X Operator Interface SD VCC-X SETPOINTS47Setpoint Screen #22 - Head Pressure Setpoints - Cooling and ReheatVCC-X Spts ID:#Head Pressure SptsC
VCC-X SETPOINTS VCC-X Operator Interface SD48Setpoint Screen #27 - Economizer Maximum Position in High CO2 Level VCC-X Spts ID:#Econo Max Pos I
VCC-X Operator Interface SD VCC-X SETPOINTS49 Reverse Acting Building Pressure Control• Outdoor Air Damper—If this option is confi gured, the VCC-X
VCC-X Operator Interface SD SYSTEM CONNECTION5Modular Service ToolWhether you have a Stand Alone, Interconnected, or Networked VCC-X Cont
VCC-X SETPOINTS VCC-X Operator Interface SD50Setpoint Screen #35 - Preheat Relay SetpointVCC-X Spts ID:#Preheat RelaySetpoint: 30.0ºFFor cold
VCC-X Operator Interface SD VCC-X SETPOINTS51VCC-X Setpoint ScreensSetpoint Screen #40 - Return Air Bypass Damper Factor SetpointVCC-X Spts ID:#Re
VCC-X SETPOINTS VCC-X Operator Interface SD52Setpoint Screen #46 - Space Sensor Calibration - Current and OffsetVCC-X Spts ID:#Space Sensor Cal
VCC-X Operator Interface SD VCC-X SETPOINTS53Setpoint Screen #49 - OAT Sensor Calibration - Current and OffsetVCC-X Spts ID:#OAT Sensor CalCurren
ZoneZoneVCC-X STATUS VCC-X Operator Interface SD54Screen #16 Current Outdoor Air Drybulb and Current Outdoor Air Relative HumidityScreen #17 C
VCC-X Operator Interface SD VCC-X STATUS55VCC-X Status Screens Status Screens - General ProceduresFrom any menu screen, press <STATUS>. The Unit
ZoneZoneVCC-X STATUS VCC-X Operator Interface SD56VCC-X Status ScreensStatus Screen #4 - Space and Return Temperature & Slide Adjust VCC-X
VCC-X Operator Interface SD VCC-X STATUS57VCC-X Status ScreensStatus Screen #9 - Heating Outputs - Active Stages and Mod Heat PositionVCC-X v1.02
ZoneZoneVCC-X STATUS VCC-X Operator Interface SD58VCC-X Status ScreensStatus Screen #14 - PREHEAT-X Controller Current Leaving Air and Entering Air
VCC-X Operator Interface SD VCC-X STATUS59Status Screen #18 - Economizer Enabled and Economizer PositionVCC-X v1.02 ID #Economizer Enabled: YE
ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD6Modular System Manager SD Modular System Manager SDENTERCLEARESCPREVNEXTDOWNUP654DEC7081329M
ZoneZoneVCC-X STATUS VCC-X Operator Interface SD60Status Screen #23 - Return Air CFM & Exhaust Air CFMVCC-X v1.02 ID # Return kCFM: XXX.
VCC-X Operator Interface SD VCC-X STATUS61Status Screen #27 - Return Air Damper Signal & Return Air Bypass Damper SignalVCC-X v2.00 ID 101 Ret
ZoneZoneVCC-X STATUS VCC-X Operator Interface SD62Status Screens #37-#41 - EM1 RelaysVCC-X v1.02 ID # Main Exp Rly 1-5 Relay NameON/OFFLine 2
VCC-X Operator Interface SD VCC-X STATUS63VCC-X Status ScreensStatus Screens #54-## - Alarm Status VCC-X v1.02 ID # NO ALARMS PRESENTVCC-X v
RSMV CONFIGURATION VCC-X Operator Interface SD64 RSMV Confi guration Setpoints Screens IndexThe available screens for the RSMV(s) are listed on the
VCC-X Operator Interface SD RSMV CONFIGURATION65RSMV Confi guration ScreensModular Service Tool InstructionsNo matter what screen or menu you’re in, pr
RSMV CONFIGURATION VCC-X Operator Interface SD66RSMV Confi guration Screens SETUP RSM STAGING COMPRESSOR SETTINGS RSMV Compressor Settings ScreensFr
VCC-X Operator Interface SD RSMV STATUS67 RSM #1-#4 Status Screen IndexThe available Status Screens for the RSMV Modules are listed by sequential scr
RSMV STATUS VCC-X Operator Interface SD68Status Screen #3 - Coil (Suction Line) Temperature 1, Superheat 1, and Expansion Valve 1 PositionRSM #
VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 69VAV/Zone Confi guration Screens VAV/Zone Confi gurationIn order to correctly set up the VAV/Z
VCC-X Operator Interface SD SYSTEM CONNECTION7Modular System Manager SD Network Connection Network ConnectionAs previously described, wh
VAV/ZONE CONFIGURATION VCC-X Operator Interface SD70VAV/Zone Confi guration Screens Confi guration Screen #3 - Voting ZoneXX Box Cnfg IDXXXXIs Th
VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 71VAV/Zone Confi guration ScreensConfi guration Screen #9 - Push-ButtonOverrideXX Box Cnfg IDX
VAV/ZONE CONFIGURATION VCC-X Operator Interface SD72VAV/Zone Setpoint Screens VAV/Zone Controller SetpointsModular Service Tool InstructionsFrom a
VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 73VAV/Zone Setpoint ScreensSetpoint Screen #3 - AHU Heat Call Space TempXX Box Spts IDXXXXAH
VAV/ZONE CONFIGURATION VCC-X Operator Interface SD74 Setpoint Screen #8 - Damper Airfl ow Night Min and Fan On Min XX Box Spts IDXXXXDamper/
VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 75VAV/Zone Setpoint ScreensSetpoint Screen #13 - Zone Alarm DelayXX Box Spts IDXXXXZone Alar
VAV/ZONE STATUS76 VCC-X Operator Interface SD VAV/Zone StatusStatus Screen #1 - Mode of OperationXX Box v4.01 IDXXXXOccupied ModeVent ModeBelongs t
VCC-X Operator Interface SD VAV/ZONE STATUS77Status Screen #5 - Zone Damper Position, Airfl ow, and Desired CFMXX Box
VAV/ZONE DAMPER FORCE VCC-X Operator Interface SD78VAV/Zone Damper Force Modes Damper Force ModesDamper Force Modes are available for testing or bal
VCC-X Operator Interface SD MINILINK PD CONFIGURATION79MiniLink PD Confi guration Screens MiniLink PD Confi gurationNOTE: I
ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD8Power/Comm Board Wiring Figure 5: Typical Power/Comm Board WiringA Power/CommOfUsing. You
ZoneZone MINILINK PD CONFIGURATION80VCC-X Operator Interface SDMiniLink PD Confi guration and Status ScreensConfi guration Screen #4 - Optimal StartTa
TROUBLESHOOTINGVCC-X Operator Interface SD 81VCC-X Outputs Force Outputs ForceOutputs Force settings are available for testing or t
ZoneZoneTROUBLESHOOTING VCC-X Operator Interface SD82Analog Output 4 Screen Exhaust Fan SignalOverride Volts: -1.0[-1.0 = Auto]The default sett
VCC-X Operator Interface SDAPPENDIX A - SAVE, LOAD, COPY SETPOINTS83Modular Service Tool InstructionsFrom any menu screen, press <BALANCE-TEST>.
APPENDIX A - SAVE, LOAD, COPY SETPOINTS84VCC-X Operator Interface SD Copy Setpoints - Network ModeTo copy a saved setpoints fi le to other controllers
VCC-X Operator Interface SD APPENDIX B - UPDATING THE SD CARD85Updating Your SD Memory CardYou may need to update your SD memory card from
APPENDIX C - UPDATING CONTROLLERS & MODULES 86 VCC-X Operator Interface SDUpdating Controller & E-BUS Module Software Using
APPENDIX C - UPDATING CONTROLLERS & MODULES87VCC-X Operator Interface SDUpdating Controller & E-BUS Module SoftwareE-BUS Modules1.
INDEX VCC-X Operator Interface SD88A-D12 Relay E-BUS Expansion Module Installed...2612 Relay E-BUS RelayConfi guration Screens...3712 Re
VCC-X Operator Interface SD INDEX89E-MEEconomizerMaximum Position if High CO2 Level Setpoint...
VCC-X Operator Interface SD SYSTEM CONNECTION9 Stand Alone ConnectionUse Supplied Modular CableWith Stripped Ends ForConnection To Termin
INDEX VCC-X Operator Interface SD90M-RMod Cool Enable Relay Description...38Mod Cool Proportional Window and Time Period...46Controllin
VCC-X Operator Interface SD INDEX91R-SMod Heat Enable...38Occupied Active...38Override
INDEX VCC-X Operator Interface SD92SSCREENS, CONTINUEDOutdoor Sensor Type...27Outputs Force Screen...81Overrides Screen...13,21Pr
VCC-X Operator Interface SD INDEX93S-VSpace Sensor Overrides Screen...21Space Sensor Slide A
INDEX VCC-X Operator Interface SD94VCC-X ControllerAlarm Conditions...63Analog Output Override...81Confi guration Screens...25Damp
NOTESVCC-X Operator Interface SD 95
Form: OR-VCCXOISD-TGD-01A Printed in the USA June 2015All rights reserved. Copyright 2015WattMaster Contr