VCC-X Controller Code: SS1062 Version 2.0 & up
VAV/Zone Controller Code: SS1001, SS1005, SS1025
Requires Service Tool SD Code: SS1063
Requires System Manager SD Code: SS1068
VCC-X Controller
Operator Interface SD
Technical Guide
www.orioncontrols.com
Vista de pagina 0
1 2 3 4 5 6 ... 95 96

Indice de contenidos

Pagina 1 - Technical Guide

VCC-X Controller Code: SS1062 Version 2.0 & upVAV/Zone Controller Code: SS1001, SS1005, SS1025Requires Service Tool SD Code: SS1063Requires Sys

Pagina 2 - IMPORTANT NOTICE

MODULAR SERVICE TOOL SD10 VCC-X Operator Interface SDModular Service Tool KeysOperator InterfacesIn order to confi gure and program the VCC-X Controlle

Pagina 3

VCC-X Operator Interface SD MODULAR SERVICE TOOL SD11Modular Service Tool InitializationModular Service Tool Initialization Screen and

Pagina 4 - Modular Service Tool SD

MODULAR SERVICE TOOL SD12 VCC-X Operator Interface SDSetting the Operating ModeThe Operating Mode is displayed on the last line of the Main Screen as

Pagina 5 - Modular Service Tool

VCC-X Operator Interface SD MODULAR SERVICE TOOL SD13Modular Service Tool Alarm SearchNOTE: When you press the <ALARMS> button o

Pagina 6 - Modular System Manager SD

MODULAR SERVICE TOOL SD14 VCC-X Operator Interface SDThe screens will step through the Start Time and then the Stop Time for each day of the week. You

Pagina 7 - Network Connection

VCC-X Operator Interface SD MODULAR SERVICE TOOL SD15 Holiday Start/Stop TimesVCC-X Schd ID #Holiday Schedule Start Event #1: XXXX

Pagina 8 - Power/Comm Board Wiring

ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD16System Manager SD Keys and ButtonsOperator InterfacesIn order to confi gure and progr

Pagina 9 - Stand Alone Connection

VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD17System Manager SD InitializationSystem Manager SD Initialization Screen and Setup ScreensA

Pagina 10 - Modular Service Tool Keys

ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD18Setting the Operating ModeSetting the Operating ModeThe Operating Mode is displayed

Pagina 11 - VCC-X Operator Interface SD

VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD19Changing PasscodesSystem Manager PasscodesChanging the mode of operation, updating software

Pagina 12

ZoneZoneSD CARD UPDATING INSTRUCTIONSThe Modular Service Tool and Modular System Manager are equipped with an SD memory card. This SD card can be remo

Pagina 13 - Alarm and Override Search

ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD20Network Mode & Multiple Managers Loop SearchWhen the System Manager is confi gu

Pagina 14 - Schedules and Holidays

VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD21 Unit Alarm Search and Override SearchAlarm ScreenNO ALARMS DETECTEDTo check controllers indi

Pagina 15

ZoneZoneMODULAR SYSTEM MANAGER SD VCC-X Operator Interface SD22 Week SchedulesFrom the Unit Schedule Menu, select Week Schedules. The following t

Pagina 16 - MODULAR SYSTEM MANAGER SD

VCC-X Operator Interface SD MODULAR SYSTEM MANAGER SD23 Holiday Start/Stop Day SelectionFrom the Unit Schedule Menu, select Holiday Schedules. Th

Pagina 17 - MODULAR SYSTEM MANAGER SD

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD24VCC-X Confi guration Screen Index VCC-X Confi guration Screen IndexThe available Confi gurat

Pagina 18 - Setting the Operating Mode

VCC-X Operator Interface SD VCC-X CONFIGURATION25 Confi guration ScreensIn order to correctly set up the VCC-X Controller, you must fi rst confi gure

Pagina 19 - Changing Passcodes

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD26VCC-X Confi guration Screens Confi guration Screen #3 - RSM #3 & #4 Modules InstalledV

Pagina 20

VCC-X Operator Interface SD VCC-X CONFIGURATION27 VCC-X Confi guration ScreensConfi guration Screen #9 - HVAC Mode Set By Remote ContactVCC-X Cnfg

Pagina 21

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD28VCC-X Confi guration ScreensConfi guration Screen #15 - Return Sensor TypeVCC-X Cnfg I

Pagina 22

VCC-X Operator Interface SD VCC-X CONFIGURATION29Confi guration Screen #22 - Fan Starting DelayVCC-X Cnfg ID #Fan StartingDelay: -1s[-1 = Unit A

Pagina 23

VCC-X Operator Interface SD 3 TABLE OF CONTENTSOVERVIEW & SYSTEM CONNECTION ...

Pagina 24 - VCC-X CONFIGURATION

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD30VCC-X Confi guration ScreensConfi guration Screen #27 - Mechanical Heat/Cool Alarm DelayVC

Pagina 25 - VCC-X Confi guration Screens

VCC-X Operator Interface SD VCC-X CONFIGURATION31VCC-X Confi guration ScreensConfi guration Screen #33 - Economizer Voltage OutputVCC-X Cnfg ID #

Pagina 26 - VCC-X Confi guration Screens

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD32Confi guration Screen #39 - Exhaust Fan OutputVCC-X Cnfg ID #Exh Fan Volts Min Volt

Pagina 27

VCC-X Operator Interface SD VCC-X CONFIGURATION33Confi guration Screen #43 - Type of Airfl ow Station VCC-X Cnfg ID #Airflow Station: ParagonUSE

Pagina 28

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD34VCC-X Confi guration ScreensConfi guration Screen #50 - Return Airfl ow Duct Size VCC-X Cn

Pagina 29

VCC-X Operator Interface SD VCC-X CONFIGURATION35Confi guration Screen #55 - Daylight Savings AdjustmentVCC-X Cnfg ID #Daylight AdjustmentStart

Pagina 30

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD36VCC-X Confi guration ScreensConfi guration Screen #62 - Broadcast to BoxesVCC-X Cnfg

Pagina 31

VCC-X Operator Interface SD VCC-X CONFIGURATION37VCC-X Confi guration ScreensConfi guration Screens #70-76 - VCC-X RelayConfi guration ScreensVCC-X C

Pagina 32

ZoneZoneVCC-X CONFIGURATION VCC-X Operator Interface SD38VCC-X Confi guration Screens Table 5: User-Confi gurable Relay OutputsNo. Relay Descripti

Pagina 33

VCC-X Operator Interface SD VCC-X CONFIGURATION39Screen #20 Mod Heat Proportional Window and Time PeriodScreen #21 Mod Cool Proportional Window

Pagina 34

ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD4Modular Service Tool SD Modular Service Tool SDThe OE391-12 Modular Service Tool is a system

Pagina 35

VCC-X SETPOINTS VCC-X Operator Interface SD40VCC-X Setpoint ScreensSetpoints - General Procedures Modular Service Tool InstructionsFrom any menu s

Pagina 36

VCC-X Operator Interface SD VCC-X SETPOINTS41Setpoint Screen #4 - Mode DeadbandVCC-X Spts ID:#Mode DeadbandSetpoint: 1.0ºFThis Setpoint is added

Pagina 37

VCC-X SETPOINTS VCC-X Operator Interface SD42Setpoint Screen #6 - Space Sensor Push-Button Override DurationVCC-X Spts ID:#Space Sensor PushBut

Pagina 38

VCC-X Operator Interface SD VCC-X SETPOINTS43Setpoint Screen #10 - Indoor RH Setpoint Low and High Reset SourceVCC-X Spts ID:#Indoor RH Setpoint

Pagina 39 - VCC-X Setpoint Screens

VCC-X SETPOINTS VCC-X Operator Interface SD44VCC-X Setpoint ScreensSetpoint Screen #13 - VFD Speed Minimums Cool/Vent ModesVCC-X Spts ID:#VFD

Pagina 40 - VCC-X SETPOINTS

VCC-X Operator Interface SD VCC-X SETPOINTS45Setpoint Screen #18 - Heat Reset Source Setpoints - High Reset/Low ResetVCC-X Spts ID:#Heat Rst Sourc

Pagina 41 - VCC-X SETPOINTS

VCC-X SETPOINTS VCC-X Operator Interface SD46Setpoint Screen #19 - Stage Off Window - Cooling/HeatingVCC-X Spts ID:#Stage Off WindowCooling: 5.

Pagina 42

VCC-X Operator Interface SD VCC-X SETPOINTS47Setpoint Screen #22 - Head Pressure Setpoints - Cooling and ReheatVCC-X Spts ID:#Head Pressure SptsC

Pagina 43

VCC-X SETPOINTS VCC-X Operator Interface SD48Setpoint Screen #27 - Economizer Maximum Position in High CO2 Level VCC-X Spts ID:#Econo Max Pos I

Pagina 44

VCC-X Operator Interface SD VCC-X SETPOINTS49 Reverse Acting Building Pressure Control• Outdoor Air Damper—If this option is confi gured, the VCC-X

Pagina 45

VCC-X Operator Interface SD SYSTEM CONNECTION5Modular Service ToolWhether you have a Stand Alone, Interconnected, or Networked VCC-X Cont

Pagina 46

VCC-X SETPOINTS VCC-X Operator Interface SD50Setpoint Screen #35 - Preheat Relay SetpointVCC-X Spts ID:#Preheat RelaySetpoint: 30.0ºFFor cold

Pagina 47

VCC-X Operator Interface SD VCC-X SETPOINTS51VCC-X Setpoint ScreensSetpoint Screen #40 - Return Air Bypass Damper Factor SetpointVCC-X Spts ID:#Re

Pagina 48

VCC-X SETPOINTS VCC-X Operator Interface SD52Setpoint Screen #46 - Space Sensor Calibration - Current and OffsetVCC-X Spts ID:#Space Sensor Cal

Pagina 49

VCC-X Operator Interface SD VCC-X SETPOINTS53Setpoint Screen #49 - OAT Sensor Calibration - Current and OffsetVCC-X Spts ID:#OAT Sensor CalCurren

Pagina 50

ZoneZoneVCC-X STATUS VCC-X Operator Interface SD54Screen #16 Current Outdoor Air Drybulb and Current Outdoor Air Relative HumidityScreen #17 C

Pagina 51

VCC-X Operator Interface SD VCC-X STATUS55VCC-X Status Screens Status Screens - General ProceduresFrom any menu screen, press <STATUS>. The Unit

Pagina 52

ZoneZoneVCC-X STATUS VCC-X Operator Interface SD56VCC-X Status ScreensStatus Screen #4 - Space and Return Temperature & Slide Adjust VCC-X

Pagina 53

VCC-X Operator Interface SD VCC-X STATUS57VCC-X Status ScreensStatus Screen #9 - Heating Outputs - Active Stages and Mod Heat PositionVCC-X v1.02

Pagina 54 - VCC-X Status Screens

ZoneZoneVCC-X STATUS VCC-X Operator Interface SD58VCC-X Status ScreensStatus Screen #14 - PREHEAT-X Controller Current Leaving Air and Entering Air

Pagina 55

VCC-X Operator Interface SD VCC-X STATUS59Status Screen #18 - Economizer Enabled and Economizer PositionVCC-X v1.02 ID #Economizer Enabled: YE

Pagina 56

ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD6Modular System Manager SD Modular System Manager SDENTERCLEARESCPREVNEXTDOWNUP654DEC7081329M

Pagina 57

ZoneZoneVCC-X STATUS VCC-X Operator Interface SD60Status Screen #23 - Return Air CFM & Exhaust Air CFMVCC-X v1.02 ID # Return kCFM: XXX.

Pagina 58

VCC-X Operator Interface SD VCC-X STATUS61Status Screen #27 - Return Air Damper Signal & Return Air Bypass Damper SignalVCC-X v2.00 ID 101 Ret

Pagina 59

ZoneZoneVCC-X STATUS VCC-X Operator Interface SD62Status Screens #37-#41 - EM1 RelaysVCC-X v1.02 ID # Main Exp Rly 1-5 Relay NameON/OFFLine 2

Pagina 60

VCC-X Operator Interface SD VCC-X STATUS63VCC-X Status ScreensStatus Screens #54-## - Alarm Status VCC-X v1.02 ID # NO ALARMS PRESENTVCC-X v

Pagina 61

RSMV CONFIGURATION VCC-X Operator Interface SD64 RSMV Confi guration Setpoints Screens IndexThe available screens for the RSMV(s) are listed on the

Pagina 62

VCC-X Operator Interface SD RSMV CONFIGURATION65RSMV Confi guration ScreensModular Service Tool InstructionsNo matter what screen or menu you’re in, pr

Pagina 63

RSMV CONFIGURATION VCC-X Operator Interface SD66RSMV Confi guration Screens SETUP RSM STAGING COMPRESSOR SETTINGS RSMV Compressor Settings ScreensFr

Pagina 64 - RSMV Confi guration Screens

VCC-X Operator Interface SD RSMV STATUS67 RSM #1-#4 Status Screen IndexThe available Status Screens for the RSMV Modules are listed by sequential scr

Pagina 65

RSMV STATUS VCC-X Operator Interface SD68Status Screen #3 - Coil (Suction Line) Temperature 1, Superheat 1, and Expansion Valve 1 PositionRSM #

Pagina 66

VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 69VAV/Zone Confi guration Screens VAV/Zone Confi gurationIn order to correctly set up the VAV/Z

Pagina 67 - RSMV Status Screens

VCC-X Operator Interface SD SYSTEM CONNECTION7Modular System Manager SD Network Connection Network ConnectionAs previously described, wh

Pagina 68

VAV/ZONE CONFIGURATION VCC-X Operator Interface SD70VAV/Zone Confi guration Screens Confi guration Screen #3 - Voting ZoneXX Box Cnfg IDXXXXIs Th

Pagina 69 - VAV/ZONE CONFIGURATION

VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 71VAV/Zone Confi guration ScreensConfi guration Screen #9 - Push-ButtonOverrideXX Box Cnfg IDX

Pagina 70 - VAV/ZONE CONFIGURATION

VAV/ZONE CONFIGURATION VCC-X Operator Interface SD72VAV/Zone Setpoint Screens VAV/Zone Controller SetpointsModular Service Tool InstructionsFrom a

Pagina 71

VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 73VAV/Zone Setpoint ScreensSetpoint Screen #3 - AHU Heat Call Space TempXX Box Spts IDXXXXAH

Pagina 72 - VAV/Zone Setpoint Screens

VAV/ZONE CONFIGURATION VCC-X Operator Interface SD74 Setpoint Screen #8 - Damper Airfl ow Night Min and Fan On Min XX Box Spts IDXXXXDamper/

Pagina 73

VAV/ZONE CONFIGURATIONVCC-X Operator Interface SD 75VAV/Zone Setpoint ScreensSetpoint Screen #13 - Zone Alarm DelayXX Box Spts IDXXXXZone Alar

Pagina 74

VAV/ZONE STATUS76 VCC-X Operator Interface SD VAV/Zone StatusStatus Screen #1 - Mode of OperationXX Box v4.01 IDXXXXOccupied ModeVent ModeBelongs t

Pagina 75

VCC-X Operator Interface SD VAV/ZONE STATUS77Status Screen #5 - Zone Damper Position, Airfl ow, and Desired CFMXX Box

Pagina 76 - VAV/Zone Status Screens

VAV/ZONE DAMPER FORCE VCC-X Operator Interface SD78VAV/Zone Damper Force Modes Damper Force ModesDamper Force Modes are available for testing or bal

Pagina 77

VCC-X Operator Interface SD MINILINK PD CONFIGURATION79MiniLink PD Confi guration Screens MiniLink PD Confi gurationNOTE: I

Pagina 78 - VAV/Zone Damper Force Modes

ZoneZoneSYSTEM CONNECTION VCC-X Operator Interface SD8Power/Comm Board Wiring Figure 5: Typical Power/Comm Board WiringA Power/CommOfUsing. You

Pagina 79

ZoneZone MINILINK PD CONFIGURATION80VCC-X Operator Interface SDMiniLink PD Confi guration and Status ScreensConfi guration Screen #4 - Optimal StartTa

Pagina 80 - MINILINK PD CONFIGURATION

TROUBLESHOOTINGVCC-X Operator Interface SD 81VCC-X Outputs Force Outputs ForceOutputs Force settings are available for testing or t

Pagina 81 - VCC-X Outputs Force

ZoneZoneTROUBLESHOOTING VCC-X Operator Interface SD82Analog Output 4 Screen Exhaust Fan SignalOverride Volts: -1.0[-1.0 = Auto]The default sett

Pagina 82 - TROUBLESHOOTING

VCC-X Operator Interface SDAPPENDIX A - SAVE, LOAD, COPY SETPOINTS83Modular Service Tool InstructionsFrom any menu screen, press <BALANCE-TEST>.

Pagina 83 - Save Setpoints - Network Mode

APPENDIX A - SAVE, LOAD, COPY SETPOINTS84VCC-X Operator Interface SD Copy Setpoints - Network ModeTo copy a saved setpoints fi le to other controllers

Pagina 84

VCC-X Operator Interface SD APPENDIX B - UPDATING THE SD CARD85Updating Your SD Memory CardYou may need to update your SD memory card from

Pagina 85 - SD Memory Card Update

APPENDIX C - UPDATING CONTROLLERS & MODULES 86 VCC-X Operator Interface SDUpdating Controller & E-BUS Module Software Using

Pagina 86 - WattMaster Controllers

APPENDIX C - UPDATING CONTROLLERS & MODULES87VCC-X Operator Interface SDUpdating Controller & E-BUS Module SoftwareE-BUS Modules1.

Pagina 87

INDEX VCC-X Operator Interface SD88A-D12 Relay E-BUS Expansion Module Installed...2612 Relay E-BUS RelayConfi guration Screens...3712 Re

Pagina 88

VCC-X Operator Interface SD INDEX89E-MEEconomizerMaximum Position if High CO2 Level Setpoint...

Pagina 89 - VAV/Zone...75

VCC-X Operator Interface SD SYSTEM CONNECTION9 Stand Alone ConnectionUse Supplied Modular CableWith Stripped Ends ForConnection To Termin

Pagina 90

INDEX VCC-X Operator Interface SD90M-RMod Cool Enable Relay Description...38Mod Cool Proportional Window and Time Period...46Controllin

Pagina 91 - Controlling Sensor Low Alarm

VCC-X Operator Interface SD INDEX91R-SMod Heat Enable...38Occupied Active...38Override

Pagina 92

INDEX VCC-X Operator Interface SD92SSCREENS, CONTINUEDOutdoor Sensor Type...27Outputs Force Screen...81Overrides Screen...13,21Pr

Pagina 93 - VAV/Zone Status

VCC-X Operator Interface SD INDEX93S-VSpace Sensor Overrides Screen...21Space Sensor Slide A

Pagina 94 - Zone Damper Position

INDEX VCC-X Operator Interface SD94VCC-X ControllerAlarm Conditions...63Analog Output Override...81Confi guration Screens...25Damp

Pagina 95

NOTESVCC-X Operator Interface SD 95

Pagina 96

Form: OR-VCCXOISD-TGD-01A Printed in the USA June 2015All rights reserved. Copyright 2015WattMaster Contr