VCC-X Operator Interface SD
VCC-X CONFIGURATION
37
VCC-X Con guration Screens
Con guration Screens #70-76 - VCC-X Relay
Con guration Screens
VCC-X Cnfg ID #
On-Board Relay (2-8)
Not Used
USE < or > TO CHANGE
Relay #1 is not con gurable as it is reserved for the Supply Air Fan.
Relays #2-#8 are con gurable for the following options (See Table
5, page 38 for Relay descriptions):
Not Used (Default) Cool Stage
Heat Stage Mod Heat Enable
Mod Cool Enable Warmup / Cooldown
ReHeat PreHeat
Low Ambient Exhaust Fan
Economizer Heat Wheel
Occupied Mode Override Mode
Alarm Active
Relays #2 through #8 can be individually con gured. Only forms
of Heating and Cooling can be con gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.
Con guration Screens #77-81 - EM1 Relay
Con guration Screens
VCC-X Cnfg ID #
EM1 Relay (1-5)
Not Used
USE < or > TO CHANGE
EM1 Relays #1-#5 are con gurable for the following options (See
Table 5, page 38 for Relay descriptions):
Not Used (Default) Cool Stage
Heat Stage Mod Heat Enable
Mod Cool Enable Warmup / Cooldown
ReHeat PreHeat
Low Ambient Exhaust Fan
Economizer Heat Wheel
Occupied Mode Override Mode
Alarm Active
Relays #1 through #5 can be individually con gured. Only forms of
Heating and Cooling can be con gured with multiple relays for
staging. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur. Default
is Not Used.
Con guration Screens #82-93 - E-BUS
12 Relay Con guration Screens
VCC-X Cnfg ID #
12 Rly Bd Relay (1-12)
Not Used
USE < or > TO CHANGE
The E-BUS 12 Relay Expansion Board Relays #1-#12 are con gu-
rable for the following options (See Table 5, page 38 for Relay
descriptions):
Not Used (Default) Cool Stage
Heat Stage Mod Heat Enable
Mod Cool Enable Warmup / Cooldown
ReHeat PreHeat
Low Ambient Exhaust Fan
Economizer Heat Wheel
Occupied Mode Override Mode
Alarm Active
Relays #1 through #12 can be individually con gured. Only forms
of Heating and Cooling can be con gured with multiple relays for
staging. If any other option is selected more than once, it will sim-
ply activate redundant relays, but no multiple staging will occur.
Default is Not Used.