PT-Link II BACnet3 Interface
10. BACNET PICS STATEMENT
71
10. BACnet PICS Statement
Segmentation Capability: None
Object Types and Optional Properties Supported
Object Type Optional Properties
Supported
Device Object Location
Description
UTC Offset
Active COV Subscriptions
Analog Input Reliability
Description
Analog Output Reliability
Description
Max_Pres_Value
Min_Press_Value
Analog Output
Binary Input Reliability
Description
Active_Test
Inactive_Test
Binary Output Reliability
Description
Active_Test
Inactive_Test
Binary Value Reliability
Description
Active_Test
Inactive_Test
Multi State Input Reliability
Description
State_Test
Multi State Output Reliability
Description
State_Test
Multi State Value Reliability
Description
State_Test
Noti cation Class Object
For all of these properties, the following applies:
1.) Does not support BACnet CreateObject
2.) Does not support BACnet DeleteObject
3.) No proprietary properties exist
Data Link Layer Options:
MS/TP master (Clause 9), baud rate up to 76.8 Kbps
MS/TP slave (Clause 9), baud rate up to 76.8 Kbps
Device Address Binding: Not supported
Character Sets Supported:
Where support for multiple character sets is indicated, this does not
imply that they can all be supported simultaneously.
ISO 10646 (UTF-8) / ANSI X3.4