PT-Link II BACnet3 Interface
3. PT-LINK CONFIGURATION
13
3.4 Changing the Con g.csv File
Figure 11: The FS-GUI Main Screen
NOTE: You may need Administration rights to perform this
function. See the Password Section, page 65.
1.) Open your web browser, and type the IP Address of the PT-Link,
which defaults to <192.168.1.24>, and press <ENTER>. The GUI
will launch. See Figure 11.
2.) In the Navigation Window on the left of the FS-GUI Screen, click
<Setup> and then click <File Transfer>. See Figure 12.
Figure 12: Navigation Window - File Transfer
3.) Refer to the File Transfer Window below (Figure 13). In the Con-
guration Tab, under Retrieve, click the con g.csv le in order to save
it to a destination and then open it.
Figure 13: File Transfer - Con guration Tab
4.) Open the con g.csv le in Notepad. See Figure 14.
WARNING: Only edit the con g.csv le using Notepad. DO
NOT use Excel. Using Excel to edit the con g.csv le will
corrupt its contents!
Figure 14: Con g.csv File