VCM-X Modular E-BUS Controller Technical Guide
OVERVIEW
5
Features
The VCM-X E-BUS series of controllers now consists of the VCM-X
Modular E-BUS Controller and the VCM-X WSHP (Water Source Heat
Pump) E-BUS Controller. The VCM-X Modular E-BUS Controller has
replaced the standard VCM-X Controller. The E-BUS versions of these
controllers now allow the various E-BUS modules to connect directly
to the VCM-X E-BUS Controllers.
Each of these types of controllers has a version applicable to AAON
®
Tulsa units and a different version applicable to AAON
®
Coil units. The
following is a breakdown of the different versions:
AAON
®
Tulsa VCM-X Modular E-BUS Controller
(OE332-23E-VCMX-MOD-A) uses software SS1030
AAON
®
Tulsa VCM-X WSHP E-BUS Controller
(OE332-23E-VCMX-WSHP-A) uses software SS1032
AAON
®
Coil VCM-X Modular E-BUS Controller
(OE332-23E-VCMX-MOD-C) uses software SS1034
AAON
®
Coil VCM-X WSHP E-BUS Controller
(OE332-23E-VCMX-WSHP-C) uses software SS1033
These controllers are designed with 7 analog inputs, 2 analog outputs,
and 5 relay outputs. Each VCM-X E-BUS Controller’s input and out-
put capabilities can be expanded with the VCM-X Expansion Module
(OE333-23-EM), the 12 Relay Expansion Module (OE358-23-12R),
and the 4 Binary Input Expansion Module (OE356-01-BI) by means of
a modular cable. Each VCM-X E-BUS Controller can be con gured for
control of VAV Units (with or without VAV/Zone Controllers), Constant
Volume Units, and Make-Up Air Units. Features include the following:
Up to a Combined Total of 20 Stages of Heating & Cooling
Modulating Cooling Output ( Copeland Digital
Scroll™ Compressor or Chilled Water Valve Control)
Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
Full Integration with the AAON
®
MODGAS Modulating
Natural Gas Controller
Full Integration with the AAON
®
MHGRV Modulating
Hot Gas Reheat Controller
Con gurable for Heat Pump Applications
Advanced Dehumidi cation Capabilities
Air Flow Monitoring of Outdoor Air, Supply Air,
and Return Air Streams
Air Flow Control of Outdoor Air Damper
Single Zone VAV Control
Primary/Secondary Heating Control
Adaptive Supply Air Reset
Micro Channel Condenser Control
Features and Applications
Selectable Control Sensor
Fan Proving Interlock
Dirty Filter Alarm
Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
Drybulb/Wetbulb Control of Economizer Operation
Building Pressure Control
Remote Override Capabilities
IAQ Economizer Reset
Title 24 Economizer Certi ed
7-Day, 2-Event-per-Day Scheduling
14 Holiday Event Scheduling
Optimal Start Scheduling
Trend Logging Capability
Static Pressure Control for Filter Loading Applications
Accepts Remote HVAC Mode Selection Via Contact
Closure On VCM-X Expansion Module
Con gurable for AAON
®
PAC and DPAC Applications
Heat Wheel - On/Off Control
Con gurable for R22 and R410-A refrigerant
Head Pressure Control (VCM-X Modular E-BUS and
VCM-X WSHP E-BUS)
Full Digital and Dual Digital Control (VCM-X Modular
E-BUS)
Water Source Heat Pump Monitoring (VCM-X WSHP
E-BUS)
Most common HVAC unit control applications can be con gured using
only the VCM-X E-BUS Controller. If the application requires more in-
puts and/or outputs, optional expansion modules are available to provide
for additional analog, binary, or digital inputs and outputs as required.
The available expansion module con gurations allow for 4 or 8 ad-
ditional binary inputs, 4 additional analog inputs, 5 additional analog
outputs, and up to 16 additional binary (relay) outputs. The various
expansion modules plug into the VCM-X E-BUS Controller by means
of a modular cable.