VCC-X Controller Technical Guide
APPENDIX C - RSMV LCD SCREENS
93
Diagnostic Screens
Diagnostic Screens
Refer to the following map when navigating through the Diagnostic
Screens. From the DIAGNSTC Screen, press <ENTER> to scroll
through the screens.
DIAGNSTC
WDOG CNT
#
PWER CNT
#
WATCH DOG TIMER
Displays the number of times the board has been reset due
to watchdog timer over ow.
POWER LOSS COUNT
Displays the number of times the board has been reset due
to power loss.
SP VLT
X.XX
SUCTION PRESSURE SENSOR VOLTAGE
Displays the current voltage of the Suction Pressure Sensor.
HP VLT
X.XX
HEAD PRESSURE SENSOR VOLTAGE
Displays the current voltage of the Head Pressure Sensor.
BIN 1 - BIN 4
ON/OFF
BINARY INPUTS #1 - #4
Displays the current status of each Binary Input.
TMP1 VLT
X.XX
COIL TEMPERATURE SENSOR 1 VOLTAGE
Displays the current voltage of the 1st Coil Temperature Sensor.
TMP2 VLT
X.XX
COIL TEMPERATURE SENSOR 2 VOLTAGE
Displays the current voltage of the 2nd Coil Temperature Sensor.