VAV/CAV/MUA Operator Interface SD
MUA II CONTROLLER STATUS
51
MUA II Status Screens
Status
The MUA Controller Status Screens are accessed by pressing the
<STATUS> button on the Modular Service Tool or Modular System
Manager. Enter the correct unit ID number of the MUA Controller
you want to con gure and press
<ENTER>. Once communication is
established, the *00* message will go away. Then
press <>. You will
then see Status Screen #1. Press
<> to scroll through the screens.
NOTE: If the *00* remains, it indicates a communication failure
to the controller.
Status Screen 1 - HVAC Mode
MUA-II v.2.01 0001
UNOCCUPIED
Vent Mode
07/16/2013 08:00 PM
Line 2 Displays one of the following:
UNOCCUPIED Remote Occupied
OCCUPIED Holiday Operations
FORCED OCCUPIED FORCED UNOCCUPIED
FORCED OUTPUT
Line 3 Vent Mode Cooling Mode
Heating Mode Dehumidi cation
Line 4 Displays one of the following:
MM/DD/YY HH:MM XX (XX = AM or PM)
Fan Starting Delay and then time will display
xx Left in WarmUp (Number of Minutes Left)
Status Screen 2 - Current Supply Air
Temperature & Supply Air Setpoint
MUA-II v.2.01 0001
Supply Air: XX.XºF
Supply Spt: XX.XºF
Line 2 Current Supply Air Temperature
Line 3 Current Supply Air Setpoint
Status Screen 3 - Current Outdoor Air
Temperature and Cooling & Heating Setpoints
MUA-II v.2.01 0001
Outdoor Air: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF
Line 2 Current Outdoor Air Temperature
Line 3 Cooling Cooling Mode Setpoint
Based on the current Occupied/Unoccupied Mode
of operation.
Line 4 Current Heating Mode Setpoint
Based on the current Occupied/Unoccupied Mode of
operation.
Status Screen 4 - Current Outdoor Air
Dewpoint, Dewpoint Setpoint & Outdoor RH
MUA-II v.2.01 0001
Dewpoint...: XX.XºF
Dewpoint Sp: XX.XºF
Outdoor RH.: 0.0%
Line 2 Current Outdoor Air Dewpoint
Line 3 Current Dewpoint Setpoint
Line 4 Current Outdoor Humidity
Status Screen 5 - Current Outdoor Air
Enthalpy, Enthalpy Setpoint & Enthalpy
Deadband
MUA-II v.2.01 0001
Enthalpy..: xx.xBTU
Enthalpy Sp: xx.xBTU
Enthalpy DB: xx.xBTU
Line 2 Current Outdoor Air Enthalpy
Line 3 Current Enthalpy Setpoint
Line 4 Current Enthalpy Deadband