Zone
Zone
Programming
SA Controller Operator Interface
24
SA Controller Con guration Screens
Con guration Screens #41-60 - Relay
Con guration Screens
SA Unit Cnfg ID 102
Relay Configurations
Rly xx: Not Used
Press “0” To Change
Relay #1 is not con gurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are con gurable for the following options:
Not Used Pre-Heater
Heat Stage Alarm
Cool Stage Override
Warmup Mode Occupied
Rev Valve WS Economizer
HGR
Relays #2 through #21 can be individually con gured. By using the
4 relay outputs available on the SA Controller, the 4 relays on the
SA Expansion Module, and the 12 relays on the 12 Relay Expansion
Module, you have the ability to con gure up to a combined total of 20
Heating Stages, Cooling Stages, and the rest of the options listed above.
Only the Heating and Cooling relays can be con gured with multiple
outputs. If any other option is selected more than once, it will simply
activate redundant relays, but no multiple staging will occur. Default
is “Not Used.”