SA Controller Operator Interface
16
MUA Unit
If you need to set up your HVAC unit for MUA operation, use the fol-
lowing values:
Con guration Section
Screen #1—Duct Static Pressure Control = “NO”
Screen #3—HVAC Mode Enable = “Entering Air”
Screen #4—HVAC Reset Source = “No Reset”
Can be con gured for Reset; see the Supply Air Setpoint Reset
section that follows before con guring.
Screen #6—Dehumidi cation Control = “YES”
Only if the unit is equipped for Dehumidi cation.
Screen #7—Dehumidi cation Priority = “YES”
Screen #8—Dehumidi cation Unoccupied = “NO”
Screen #9—Entering Air Humidity Sensor = “YES”
Only if equipped with an Entering Air Humidity Sensor for
Dehumidi cation.
Screen #14—Proof of Flow Input = “YES”
Only if equipped with a Proof of Flow Switch.
Screen #28— Emergency Shutdown Input = “YES”
Only if a Smoke Detector, Firestat, or other Shutdown device is
connected to the SA Controller.
Screens #41 through #60 = Refer to the AAON
®
wiring diagram
inside the unit before con guring onboard and expansion board
relays.
Heat Pump
Heat Pumps can be con gured as VAV, C AV, o r MUA. Con guration
Screens #26 and #27 are used to con gure the Heat Pump. A Relay Out-
put must be con gured for a Reversing Valve on Screens #41 through
#60 whether the Reversing Valve is to be activated during Heating or
Cooling operation. When using AAON
®
equipment, if the equipment
is an AAON
®
packaged unit, the Reversing Valve activates during
Heating operation.
Con guration Section
Screen #26—Heat Pump Control = “YES”
Screen #27—Reversing Valve Active During Heat/Cool =
“0=Heat” if the Reversing Valve should energize for Heating
operation; “1=Cool” if the Reversing Valve should energize for
Cooling operation.
Screens #41 through #60 = Refer to the AAON
®
wiring diagram
inside the unit before con guring on-board and expansion board
relays.
MUA and Heat Pump Con gurations