Lead/Lag Controller Technical Guide
Section 4: Con guring Analog Inputs
15
Sensor Reading, Scaling, and Override Duration
Sensor Reading Appendix
Select from the drop down list in the <Sensor Reading Appendix>
eld (Figure 13) to give the sensor reading a quali er.
None: No Appendix Required
RH%: Humidity Percentage
%: Percentage
°F: Fahrenheit
°C: Celsius
PPM: Parts per Million
PSI: Pound per Square Inch
“WG: Inches of Water Gauge
: Inches
Ft.: Feet
RPM: Revolutions per Minute
VDC: Volts D.C.
BTU: British Thermal Unit
CFM: Cubic Feet per Minute
Hr: Hours
Min: Minutes
GPM: Gallons per Minute
kPa: Kilopascals
Sensor Scaling
Figure 13: Sensor Reading Appendix Field
Figure 14: Sensor Scaling Field
All readings are user-scalable according to the number of digits
to the right of the decimal point. See Figure 14 and values and
examples below.
X 1 65°F
X 10 65.5°F
X 100 65.54°F
X 1000 65.543°F
Number of Readings to Average
This function has the capability of averaging up to 25 sensor readings
before it displays a new value on one of the Lead/Lag Controller
Status Screens. Sensor values are read once per second.
Type the number of readings from this sensor you want to aver-
age in the <Number of Readings to Average> eld and press
<ENTER> to save. See Figure 15. Valid entries are from 1-25.
If you want the input sensor to only show its most current reading,
enter <1>.
Figure 15: Number of Readings to Average Field
User Scaling
The User Scaling Box allows you to set a Maximum and Minimum
Reading for the speci c 4-20 mA or 0-5 vdc sensor you are using.
This means you can display values with ± 1, ± 0.1, ± 0.1± 0.01 or
higher resolutions. Just keep in mind that the maximum value that
can be sent from the controller is ±30,000, so if you have scaled your
reading to ± 0.001, then the maximum value you can send is ± 30
with the 3 additional decimal values (30.000). See Figure 16. Type
in the values and press <ENTER> to save.
Figure 16: User Scaling Box