Section 4: Con guring Analog Inputs
Lead/Lag Controller Technical Guide
14
Analog Input Con guration Screen
Con guring Analog Inputs
Left-click in the data entry eld in the Analog Inputs Window to open
the Analog Input Con guration Window (Figure 12).
The eight analog inputs can be con gured in several different ways.
Generally, the rst four inputs are the only ones used for Lead/Lag
control. These inputs can be used to generate an alarm and switch
from one device to another if the rst cannot maintain a temperature
or PSI setpoint. The others can be used to monitor various inputs.
The controlling devices can be set up to look at one sensor or each
device can have its own sensor.
The following con gurations are available for each Analog Input:
Not Used
Thermistor Fahrenheit Temperature: 10K Ohm Type III
Scaled for Fahrenheit. Set jumper to the appropriate setting
(see Figure 2, page 6).
Thermistor Celsius Temperature: 10K Ohm Type III
Scaled for Celsius. Set jumper to the appropriate setting (see
Figure 2, page 6).
4 - 20mA User Scaled: 4-20mA User-Scaled Sensor. Set
jumper to the appropriate setting (see Figure 2, page 6).
0 - 5vdc User Scaled: Select this option if using a 0-5vdc
scaled sensor. Set jumper associated with this input to the
appropriate 0-5v setting (see Figure 2, page 6.)
Read Global Analog Broadcast Channel from Another
Controller
Communicating Temperature Sensor ( OE217-02):
If using a WattMaster Communicating Temperature
Sensor with a modular cable, con gure this input to read
the appropriate Communicating Sensor Address. Enter
an address from 1-8 in the < Communicating Sensor
Address>
eld and press <ENTER>.
Communicating Humidity Sensor ( OE217-03): If using
a combination Temperature and Humidity Communicating
Sensor with a modular cable, con gure one input to read
the temperature and another input to read the humidity,
both using the same Communicating Sensor address. Enter
an address from 1-8 in the <Communicating Sensor
Address>
eld and press <ENTER>.*
Communicating Carbon Dioxide Sensor ( OE256-05
or OE256-07)
: If using a WattMaster Communicating CO
2
Sensor with a modular cable, con gure this input to read
the appropriate Communicating Sensor Address. Enter
an address from 1-8 in the <Communicating Sensor
Address>
eld and press <ENTER>.*
*NOTE: See the E-BUS Digital Room Sensor Technical Guide,
E-BUS Wall-Mounted CO
2
Sensor Technical Guide,
or E-BUS Duct-Mounted CO
2
Sensor Technical Guide
for information on how to address the communicat-
ing sensors.
Figure 12: Analog Input Con guration Window