PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
37
Appendix D - VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Parameter Name Object Description
Limits
Static
Pressure
Setpoint
StatPrSt AV:290 Current Static
Pressure
Setpoint.
.10 3.0
Supply Air
CFM
SaCFM AI:195 Current Supply
Airfl ow
Measurement.
Supply Air
Cooling
Setpoint
SaClSt AV:77 Supply Air
Setpoint in
Cooling Mode.
30 80
Supply Air
Cool High
Reset
SaClRt AV: 324 High Supply
Air Cooling
Reset Limit
40 150
Supply Air
Heat High
Reset
SaHtRt AV: 325 High Supply
Air Heating
Reset Limit
40 150
Supply Air
Heating
Setpoint
SaHtSt AV:78 Supply Air
Setpoint in
Heating Mode.
40 240
Supply Air
Temperature
SaTp AI:83 Current value
of the
supply air
temperature
sensor.
Supply Air
Temperature
Offset
SaTpOst AV:80 If the Supply
Air
Temperature
Sensor is read-
ing incorrectly,
you can use this
option to enter
an offset
temperature to
adjust the
Sensor’s
Temperature.
-100 100
Current
Supply Air
Temperature
Setpoint
SaTpStM AI: 82 Current SAT
Cooling or
Heating
setpoint if there
is no reset
source;
Current
calculated SAT
setpoint with
Reset Source.
BACnet Properties for the VCB-X Controller
Parameter Name Object Description
Limits
Unoccupied
Cooling
Offset
UnClOst AV:124 During the
Unoccupied
Mode of
Operation, this
Setpoint offsets
the
Occupied Cool-
ing Setpoint
out by this
user adjust-
able amount.
If you do not
want Cooling to
operate during
the Unoccupied
Mode, use the
default setting
of 30°F for this
setpoint.
030
Unoccupied
Heating Offset
UnHtOst AV:125 During the
Unoccupied
Mode of
Operation, this
Setpoint offsets
the
Occupied
Heating
Setpoint out by
this user adjust-
able amount.
If you do not
want Heating to
operate during
the Unoccupied
Mode, use the
default setting
of 30°F for this
setpoint.
030
VFD
Position
VfdBwPos AI:88 Current
position of the
VFD blower
fan signal.
Remote VFD
Position
Setpoint
FrcFanSp AV: 266 Override to
force the VFD
to this percent-
age speed.
Confi guring
“Auto” will
restore normal
unit control of
the VFD speed.
0% 100%
Auto=65535
OnBoard
Relay
Status
OnRlys AI:44 See page 39.
On Board
Relay 1
OnRly1 BI: 127 Current status
of VCB-X
Main Board
relay 1.
Revised 4/3/12