WSHP-X Module
Technical Guide
16
Start-Up & Commissioning
General
In order to have a trouble free start-up, it is important to follow a few
simple procedures. Before applying power for the rst time, it is very
important to run through a few simple checks.
One of the most important checks to make before powering up the
system for the rst time is to make sure that the VCM-X WSHP Series
Controller or SA Series Controller is con gured properly for your ap-
plication. Refer to the VCM-X Controller Technical Guide, VCM-X
Modular E-BUS Controller Technical Guide, SA Controller Technical
Guide, or SA E-BUS Controller Technical Guide for more information.
A handheld Modular Service Tool, Modular System Manager, or System
Manager Touch Screen connected to the VCM-X WSHP Series Control-
ler or SA Series Controller will allow you to con gure your application.
Refer to the VCM-X Operators Interfaces Technical Guide, SA Operator
Interfaces Technical Guide, or System Manager TS Technical Guide for
more information.
NOTE: The SA Series Controller does not utilize the System
Manager Touch Screen.
Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Con rm
that all sensors required for your system are mounted in the appropriate
location and wired into the correct terminals.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to
observe polarity could result in damage to the
boards.
Table 1: Unit Con gurations Chart
UNIT CONFIGURATIONS
PERMUTATION
SYSTEM A SYSTEM B
VCM-X WSHP
CONFIGURATION
SA
CONFIGURATION
Comp A1 Comp A2 Comp B1 Comp B2
Relay 1 Relay 2 Relay 3 Relay 4
1 On/Off On/Off
2 Compressors
2 Digital On/Off
2 Compressors
Digital Compressor
2 Compressors
Single Unit SA
3 Digital Digital
2 Compressors
Full Digital
2 Compressors
Single Unit SA
4 On/Off On/Off On/Off On/Off 4 Compressors
5 Digital On/Off On/Off On/Off Not Available
6 Digital On/Off Digital On/Off
4 Compressors
Digital Compressor
4 Compressors
Dual Unit SA
7 Digital Digital Digital Digital
4 Compressors
Full Digital
4 Compressors
Dual Unit SA
In the Cooling Mode, the Compressors will stage in the following order:
Permutations 1, 2 & 3: Compressor A1 -> Compressor A2
Permutations 4: Compressor A1 -> Compressor B1 -> Compressor A2 -> Compressor B2
Permutations 6: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2
Permutations 7: Compressor A1 & Compressor B1 -> Compressor A2 & Compressor B2
In the Dehumidi cation Mode, the Compressors will stage in the following order:
Permutation 4: Compressor A1 & Compressor B1 -> Compressor A2 -> Compressor B2
All other permutations in the Dehumidi cation Mode stage as described in the Cooling Mode.