Orion-system VCM-X E-BUS Component Manual de usuario Pagina 60

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 128
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 59
Zone
Zone
Modular & Non-Modular VAV/Zone Controller Wiring
VCM-X Component & Systems Wiring
60
FILENAME
DATE:
S. Olson
DESCRIPTION:
PAGE
JOB NAME
ZCAP-MOD-Main-Wire-1A.CDR
1 of 1
01/16/13
OE742-31 & OE744-31 VAV/Zone Controller
Wiring DetailsActuator Package
10
OE282
POWER / CO
O
MM
REC
Power/Comm Cable To Next
VAV/Zone Controller Actuator
Package, System Manager Or
Power/Comm Distribution Board
Power/Comm Cable From Previous
VAV/Zone Controller Actuator
Package, System Manager Or
Power/Comm Distribution Board
Connector Not Used
With This Product
Damper Actuator
Damper Actuator Cable
OE210-02, OE211-02, OE212-02
Or OE213-02 Modular Room Sensor
Display
Override
OVERRIDE ALARM
OE217-00 / OE217-01
Digital Room Sensor
Wiring When Using A Modular Sensor
Wiring When Using A Digital Room Sensor
OE325-01 Fan & Reheat
Expansion Module
(See Reheat Board Wiring For
Detailed Wiring Connections)
Connect FRP Tubing (By Others) To Terminal
Unit Air Flow Pickup Tube Hi & Lo Ports
(P.I. VAV/Zone Controller Packages Only)
This Expansion Module Is
Only Required For Single
Duct Terminal Units With
Reheat And All Fan
Terminal Units
Modular Expansion Cable
Supplied With OE325-01 Expansion Module
FMRSC Cable
TSDRSC Cable
TSDRSC Or FMRSC Cable As Required.
Select Cable Depending On Sensor(s)
Used. See Notes Above For Details
Optional - Supply Air Temperature
Sensor. Only Required When The Orion
VCM-X Controller Is Not Installed On The
HVAC Unit Connected To The Terminal
Units.Locate In Ductwork Downstream Of
The Terminal Unit
Note: The Total Length Of Cable
Cannot Exceed 160 Feet.
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLER ACTUATOR
PACKAGE
ZONE EXPANSION
YS102252 REV 1
WATMASTER CONTROLS INC.
MADE IN USA
Rc
R1
R2
R3
R4
AOUT
GND
RELAYS
ANALOG
OUTPUT
STAT
THERM
4-20mA
0-10V
0-5V
GND
AIN
ANALOG INPUT
VREF
EXPANSION IN
PWR
PIC18F4520
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
10A250VAC ~
5A30VDC
SA
VDE
G5Q-1A4
OMRON
DC24V
CHINA
COMM
Note: The Total Length Of Cable
Cannot Exceed 160 Feet.
Modular VAV/Zone Controller Actuator Package Wiring
Figure 39: OE742-31 & OE744-31 - Modular Zone Controller Actuator Package - P.I. & P.D. Wiring