Two Condenser Head Pressure Module
Technical Guide
22
Appendix for Version 1.04 and Earlier
Table 10: OPTIONS Dip Switch/Head Pressure Setpoint Settings for Stand-Alone Operation
OPTIONS Dip
Switch Settings
Head Pressure Setpoint
Air Cooled Condenser Water Cooled Condenser
Binary Value R410-A R22 R410-A R22
0 340 (DEFAULT) 200 (DEFAULT) 235 (DEFAULT) 145 (DEFAULT)
1 260 160 210 110
2 270 170 220 120
3 280 180 230 130
4 290 190 240 140
5 300 200 250 150
6 310 210 260 160
7 320 220 270 170
8 330 230 280 180
9 340 240 290 190
10 350 250 300 200
11 360 260 310 210
12 370 270 320 220
13 380 280 330 230
14 390 290 340 240
15 400 300 350 250
NOTE: R22 refrigerant can only be used with the Two Condenser Head Pressure Module versions 1.01 through 1.04.
You must cycle power after setting Dip Switch values.