Zone
Zone
Appendix
38
HB Controller Technical Guide
Condenser Fan Control Setpoints
Description Min. Default Max.
Liquid Line Cut Out Temperature 75ºF 85ºF 95ºF
Liquid Line Cut In Temperature 95ºF 105ºF 115ºF
Table 12: Condenser Fan Control Setpoints
Miscellaneous Control Setpoints
Description Min. Default Max.
Force Mode Timer 1 Min 60 Min 240 Min
Table 13: Miscellaneous Control Setpoints